GENSET MODEL LP500 KVA Rating 500
GENERATOR SPECIFICATIONS
-
Power Rating* (kVA) 500
-
Rated Current (Amps) 695
-
Dimesions Of Dg Set (L X W X H) (Mm)
-
Dimesions Of Dg Set With Acoustic
(L X W X H) (Mm) 6200 x 2100 x 2370
-
DG Weight (With Ae Upto 750 Kva)(Kg) 6700
ENGINE SPECIFICATIONS
-
Engine Make "PERKINS"
-
Engine Model 2506D-E15TAG2
-
Aspiration TA
-
Engine Rpm 1500
-
No Of Strokes 4
-
Gross Engine Out Put (Kwm) 451
-
Gross Engine Out Put (Bhp) 605
-
Displacement 15.2
-
No Of Cylinders & Configuration 6 & INLINE
-
Bore X Stroke (Mm) 137 x 171
-
Compression Ratio 18:01
-
Piston Speed (M/Sec) 8.6
-
Bemp (Kpa) 2396
FUEL SYSTEM
-
Fuel & Fuel Specification HSD - II , CALORIFIC VALUE 10200 KCAL/KG, SPECIFIC GRAVITY 855 GRM/LTR +5% TOLERANCE
-
Fuel Consumption At 100%/75% (Ltrs/Hr) 106/82
-
Specific Fuel Consumption Grms/Bhp-Hr At 100% Load 150
-
Specific Fuel Consumption Grms/Kw-Hr At 100% Load 209
-
Governor / Class ELECTRONIC / A1
-
Fuel Injection Type MEUI - MECHANICALLY ACTUATED ELECTRONICALLY CONTROLLED.
-
No Of Fuel Filters (Nos) 2
-
Fuel Filters Replacement 500 HRS OR 12 MONTHS WHICH EVER IS EARLIER
-
Type Of Fuel Filter SPIN ON PAPER ELEMENT FILTERS
-
Fuel Tank Capacity (Ltrs) 990
LUB OIL SYSTEM
-
Lub Oil Capacity Max (Ltrs) 53
-
Lub Oil Capacity Min (Ltrs) 45
-
Type Of Lub Oil Filter SPIN ON PAPER ELEMENT FILTERS
-
No Of Lube Oil Filters (Nos) 1
-
Lub Oil Filters Replacement 500 HRS OR 12 MONTHS WHICH EVER IS EARLIER
-
Lub Oil Consumption (Ltrs/Hr) 0.11
COOLING SYSTEM
-
Coolant Capacity (Engine + Rad)(Ltrs) 48
-
Radiator Cooling Air Flow(Cfm) 22306
-
Radiator Fan Power(Kw) 10
EXHAUST SYSTEM
-
Exhaust Pipe Dia At Silencer (Min)(Mm) 200
-
Max Allowed Back Pressure(Mbar) 68
-
Exhaust Gas Temperature (Deg C) 420
AIR SYSTEM
-
No Of Air Filters 1
-
Type Of Air Filter DRY TYPE PAPER ELEMENT FILTERS
-
Air Filters Replacement 1000 HRS OR 12 MONTHS WHICH EVER IS EARLIER
-
Air Intake Restriction (Mbar) 37-62
-
Battery Qty (Nos) 2
-
Battery Voltage / Current (V/Ah) 12 / 150
ENGINE CONTROLLER*
-
Alternator "LEROYSOMER/STAMFORD" MAKE SINGLE BEARING, 415 V, 50 Hz, 0.8 PF, BRUSH LESS & SELF EXCITED, IP 23 ENCLOSURE, CLASS H/H INSULATION